A new control system for the capacitive energy storage of the GOL-3 multiple-mirror trap. / Mekler, K. I.; Burdakov, A. V.; Gavrilenko, D. E. et al.
In: Instruments and Experimental Techniques, Vol. 60, No. 3, 01.05.2017, p. 345-350.Research output: Contribution to journal › Article › peer-review
}
TY - JOUR
T1 - A new control system for the capacitive energy storage of the GOL-3 multiple-mirror trap
AU - Mekler, K. I.
AU - Burdakov, A. V.
AU - Gavrilenko, D. E.
AU - Garifov, S. S.
AU - Postupaev, V. V.
AU - Rovenskikh, A. F.
PY - 2017/5/1
Y1 - 2017/5/1
N2 - A new control system for capacitive energy storage with a rated energy content as high as 16 MJ is described. Capacitive energy storage has been used since 1987 to supply power for the pulsed magnetic system of the GOL-3 multiple-mirror trap. It has an operating voltage of 6 kV and consists of 6000 IK-6-150 capacitors that are located in six remote rooms together with the necessary infrastructure. The system for control and data acquisition was built using Arduino microcontroller boards operating as a distributed network of remote servers. The client part of the control system uses a personal computer with a standard configuration; communication with remote servers is effected by the TCP/IP protocol. The control system was put into regular operation at devices of the GOL-3 facility in the early 2016.
AB - A new control system for capacitive energy storage with a rated energy content as high as 16 MJ is described. Capacitive energy storage has been used since 1987 to supply power for the pulsed magnetic system of the GOL-3 multiple-mirror trap. It has an operating voltage of 6 kV and consists of 6000 IK-6-150 capacitors that are located in six remote rooms together with the necessary infrastructure. The system for control and data acquisition was built using Arduino microcontroller boards operating as a distributed network of remote servers. The client part of the control system uses a personal computer with a standard configuration; communication with remote servers is effected by the TCP/IP protocol. The control system was put into regular operation at devices of the GOL-3 facility in the early 2016.
UR - http://www.scopus.com/inward/record.url?scp=85021177752&partnerID=8YFLogxK
U2 - 10.1134/S0020441217030228
DO - 10.1134/S0020441217030228
M3 - Article
AN - SCOPUS:85021177752
VL - 60
SP - 345
EP - 350
JO - Instruments and Experimental Techniques
JF - Instruments and Experimental Techniques
SN - 0020-4412
IS - 3
ER -
ID: 8975861